top of page

WD4000

Medium Voltage Variable Frequency Drives (VFD)

 

Wolong is a leading manufacturer of high-voltage drives with 25 years of experience and a global installed base for industrial pump, fan, blower, compressor, and conveyor applications.

 

We offer essential VFDs to help reduce energy consumption and ease maintenance costs for the Mining, Oil & Gas, Water & Wastewater, Power Generation, and general processing industries.

Wolong Drive Image.png

Advantages

Best-in-class 18-pulse phase shift transformer as standard starting at 1000 HP.
  • Performs with low distortion which lowers harmonics for the local grid, exceeding IEEE 519 and most utility codes.

Cascaded H-Bridge is a proven state-of-the-art topology featuring:
  • An IGBT based multi-level voltage source inverter delivering low distortion output.

  • This design eliminates the need for filters and can control legacy as well as modern motors.

  • It is superior to 2 or 3 level inverters and far superior to current source inverter designs.

  • High system reliability with neutral rebalancing. The drive will continue to run if a power module fails so an operator can plan a controlled shutdown.

  • Maintenance is easy with a modular design, allowing fast swap out of power modules. The design also allows front access to all components.

Industry-leading power density for an optimal footprint
  • This high power dense system optimizes floor space, and the modular/drawer structure is easy to maintain.

Fast lead times

Features

Technical Scope
  • 4160 V

  • 1000 - 5500 HP

  • 130 - 635 Amps

  • Input Voltage - 4160V ±10%, optionally 3.3 - 13.8kV

  • Input Voltage Frequency - 50/60 Hz, ±5%

!
Widget Didn’t Load
Check your internet and refresh this page.
If that doesn’t work, contact us.
Type
Rated Motor Voltage (kV))
Current (A)
Shaft Output (HP)
Shaft Output (kW)
WD4000-4-130
4.16
130
1000
746
WD4000-4-159
4.16
159
1250
933
WD4000-4-190
4.16
190
1500
1119
WD4000-4-222
4.16
222
1750
1306
WD4000-4-254
4.16
254
2000
1492
Features
Technical Specifications
Application
Fans, pumps, compressors, blowers, conveyors
Power semiconductors
IGBT’s; Diodes
Input voltage
4160V ±10%, optionally 3.3 - 13.8kV
Input overvoltage (swell)
20%
Input undervoltage (dip or sag)
-34%, continues operation with reduced torque
Input voltage frequency
50/60Hz, ±5%
Line-side rectifier
18 pulse diode rectifiers
Input power factor
≥0.95, load >10%
Input current harmonics
Meet IEEE519
Motor-side inverter
Multi-level inverter (PWM) with IGBT power modules
Output cable length
No filter needed if less than 2.2km
Output voltage
4/4.16kV
Output frequency and drift
0.5 ... 330 ± 0.5 % (sensor-less or open loop vector control), or ± 0.1 % with encoder (encoder or closed loop vector control)
Drive quadrants
2
Drive control methods
Sensor-less vector control, encoder vector control, VF control, open loop control, close loop control
Page 1 of 3

Medium Voltage
Variable Frequency Drives Flyer

Medium Voltage
Variable Frequency Drives Brochure

bottom of page